| LPL | Rolling sphere R | Mesh | Typical |
|---|---|---|---|
| I | 20 m | 5×5 m | Flammable |
| II | 30 m | 10×10 m | Process plant |
| III | 45 m | 15×15 m | Ordinary |
| IV | 60 m | 20×20 m | Low risk |
Rolling sphere of radius R touches where air terminals are needed; all parts must match the same LPL.
Run a risk assessment (IEC 62305-2) to pick the Lightning Protection Level (LPL I–IV; I is most onerous, for flammable plant). The LPL fixes the rolling-sphere radius (I=20 m, II=30 m, III=45 m, IV=60 m) and mesh size for the air termination, the down-conductor spacing, and the SPD class. Provide a low-impedance ring earth (≤10 Ω), bond all metal & services, and fit Type 1+2 SPDs at the LV main.
IEC 62305 (-1 general, -2 risk, -3 physical damage, -4 electrical/electronic), NFPA 780, API RP 545 (tanks).
Standards — IEC 62305 (1–4); NFPA 780; API RP 545.