| Type | Measures vs | Use for |
|---|---|---|
| Gauge | Atmosphere | Most process |
| Absolute | Vacuum | Vacuum systems |
| Differential | Two points | Flow / level / filters |
Normal at ~60% of span gives surge headroom; over-ranging wastes resolution where you operate.
Reference: gauge for most process; absolute for vacuum / vapour pressure; differential for flow, level & filters. Size the range so the normal operating pressure is ~50–75% of span (never >90%), respecting the transmitter turndown. Add a remote/diaphragm seal for viscous, clogging, corrosive or high-temperature fluids. Default output 4–20 mA + HART; SS316L wetted parts unless the fluid demands better.
IEC 61298 (instrument performance), EN 837 (pressure gauges), ASME B40.100, ISA-RP for installation.
Standards — IEC 61298; EN 837; ASME B40.100; ISA-RP.
We select pressure instruments & specify seals and manifolds.