| Type | Best for | Notes |
|---|---|---|
| Spring-diaphragm | Modulating control | Inherent fail action |
| Piston | High thrust | Accumulator for fail-safe |
| Electric | No air available | Fail-last by default |
| Hydraulic | Very high force | Complex |
Actuator must beat ΔP × seat area + friction + seat load at worst-case ΔP, with margin.
Modulating control with fail-safe → pneumatic spring-diaphragm + smart positioner (the default). Quarter-turn on/off → pneumatic piston (rack & pinion / scotch yoke). No instrument air, or precise positioning / high thrust → electric. Very high force → hydraulic / electro-hydraulic. Always size thrust ≥ required to seat against full ΔP with margin, set the correct fail action (FC/FO/FL), and add ESD partial-stroke testing on safety valves.
IEC 60534-6 (actuator mounting), ISA 75, API 6D (pipeline valve actuators), IEC 61508/61511 for ESD/PST.
Standards — IEC 60534-6; ISA 75; API 6D; IEC 61508/61511.