
| Hazard | Detector | Why |
|---|---|---|
| HC gas | IR point / open-path | No poisoning |
| H₂ / others | Catalytic | IR blind to H₂ |
| Toxic | Electrochemical | ppm sensitivity |
| Fire | Flame + smoke/heat | Flame & smoke |
Coverage (not fixed spacing) drives layout; 2ooN voting avoids false trips; two-stage alarm/trip.
Match detector to hazard: hydrocarbon gas → IR point (no poisoning) or open-path IR for wide areas; H₂/some gases → catalytic; toxic (H₂S, CO) → electrochemical (ppm); fire → UV/IR flame, plus smoke/heat indoors. Lay out for ≥ 90% geographic coverage (or scenario/dispersion mapping). Use 2ooN voting to confirm before tripping. Set 20% LEL alarm / 40% LEL executive action (ESD, deluge) and design the F&G to the required SIL.
IEC 60079-29 (gas detectors), ISA 84 / IEC 61511 (F&G integrity), NFPA 72 (fire alarm), EN 50402, ISA TR84.00.07 (F&G effectiveness).
Standards — IEC 60079-29; ISA 84 / IEC 61511; NFPA 72.
We design F&G layouts & cause-and-effect to ISA 84.