| Purpose | Drives |
|---|---|
| Heat conservation | Economic thickness. |
| Personnel protection | Surface ≤ 60°C. |
| Anti-condensation | Surface > dew point + barrier. |
| Acoustic / fire | Special / rated systems. |
| Material | Range | Notes |
|---|---|---|
| Mineral / rock wool | up to ~650°C | General hot service. |
| Calcium silicate | up to ~650°C | Rigid, abuse-resistant. |
| Cellular glass | −200 to 430°C | Cold / cryogenic. |
| PIR / PUR foam | −180 to 120°C | Cold service. |
| Aerogel | up to ~650°C | Thin, high-performance. |
Iterate thickness to meet the surface target; finalize with 3E-Plus.
Hot service → mineral wool (to ~650°C) or calcium silicate (rigid, abuse-resistant). Cold service → cellular glass or PIR/PUR with a vapour barrier. Personnel protection → enough thickness to keep the surface ≤ 60°C. Cladding: aluminium (indoor), stainless (corrosive/wash-down). Always vapour-seal cold lines.
ASTM C547/C533/C552 (materials); CINI / project insulation spec; economic & surface-temperature thickness by 3E-Plus (ASTM C680 method).
Standards — ASTM C547/C533/C552; CINI; ASTM C680 (3E-Plus).
We calculate thickness, surface temp and CUI protection.