| Need | Choose | Why |
|---|---|---|
| Single, robust | 4-20 mA + HART | Proven + diagnostics |
| Many devices | Foundation Fieldbus / PA | Multidrop |
| Packaged gear | Modbus RTU/TCP | Universal serial |
| High-speed digital | PROFINET / Ethernet-APL | Ethernet to field |
Live-zero at 4 mA means a broken wire (0 mA) ≠ a real zero — NE43 makes faults auto-detectable.
Single robust loop, simple & familiar → 4-20 mA + HART (the default; HART gives diagnostics over the same pair). Many devices per cable, less wiring → Foundation Fieldbus H1 or PROFIBUS PA. Packaged/serial equipment → Modbus. New high-speed, long-distance digital → PROFINET / Ethernet-APL. Safety functions → keep them hardwired or on a certified safety bus, not on the basic control bus.
NAMUR NE43 (signal fault levels), NE107 (diagnostics), IEC 61158/61784 (fieldbus), HART/FF/PA specs, IEC 61511 for safety signalling.
Standards — NAMUR NE43 / NE107; IEC 61158/61784; IEC 61511.
We design signalling & network architecture with safety segregation.