Selecting Circuit Breakers

Carry the load, trip on fault, safely interrupt — rated current & breaking capacity rule.

Back to Knowledge Hub
Quick pick (TL;DR)
  • Pick the type by current & voltage: MCB (≤125 A final circuits), MCCB (up to ~1600 A LV feeders/motors), ACB (large LV mains), VCB (MV switchgear).
  • Then rated current In ≥ load, set trip Ir to protect the cable, and the breaking capacity Icu ≥ the prospective fault current.
  • Use electronic LSIG trip units for selectivity on feeders.

Step 1 — Choose the type

TypeRangeUse for
MCB≤ 125 A, LVFinal circuits
MCCB~16–1600 A, LVFeeders, motors
ACB~630–6300 A, LVMain incomers
VCBMV (3.3–36 kV)MV switchgear

Step 2 — Worked selection

90 kW motor, 31 kA fault
Given load current = 166 A prospective fault = 31 kA Step 1 — Rated current In ≥ load → In = 250 A frame Step 2 — Trip setting Ir set to protect cable (Iz 340 A) load 166 ≤ Ir 210 ≤ Iz 340 → OK Step 3 — Breaking capacity Icu ≥ fault current Icu 36 kA ≥ 31 kA → OK Answer MCCB 250 A, Ir 210 A, Icu 36 kA, LSIG

Order: type → In → trip → Icu ≥ fault. Never compromise on Icu.

Step 3 — Trip units & selectivity

  • Thermal-magnetic: simple, fixed.
  • Electronic LSIG: adjustable, selective.
  • Category B for selective feeders.

Breaker selection calculator

Rated current & breaking capacity
In ≥ load; Ir between load & cable Iz; Icu ≥ fault.
LV MCCB screening — Icu must exceed fault. Use LSIG trip for selectivity.

Common mistakes

  • Icu below the fault level.
  • Trip above cable capacity.
  • No selectivity → nuisance blackouts.

Requisition & datasheet

  • Load, voltage, current, fault.
  • Type, In, Ir, Icu, poles, trip unit.

Frequently asked questions

What should I know about Selecting Circuit Breakers?

Pick the type by current & voltage: MCB (≤125 A final circuits), MCCB (up to ~1600 A LV feeders/motors), ACB (large LV mains), VCB (MV switchgear). Then rated current In ≥ load, set trip Ir to protect the cable, and the breaking capacity Icu ≥ the prospective fault current. Use electronic LSIG trip units for selectivity on feeders.

Which standards or codes apply?

IEC 60947-2 (LV breakers), IEC 62271-100 (MV breakers), UL 489, IEC 60909 (fault current).

Standards — IEC 60947-2; IEC 62271-100; UL 489; IEC 60909.