
| Method | Start current | Start torque | Use for |
|---|---|---|---|
| DOL | 6–7× FLC | Full | Small motors |
| Star-delta | ~⅓ (2–3×) | ~⅓ | Light-start loads |
| Soft starter | 2.5–4× | Controlled | Pumps, fans |
| VFD | ~1–1.5× | Controlled | Speed control |
Volt-dip ≈ start current ÷ source fault level. DOL dips 18%; soft starter keeps within limits.
Small motors / strong supply → DOL (simplest, full torque). Medium with light start → star-delta (cuts inrush to ~⅓ but only ⅓ torque). Pumps/fans where you want a smooth ramp & less inrush → soft starter. Need speed control, energy saving or high inertia → VFD. Always check the supply can hold voltage dip within ~15% during start.
IEC 60947-4-1 (starters & contactors), IEC 60034 (motors), IEC 61800 (VFD drives), NEMA ICS 2.
Standards — IEC 60947-4-1; IEC 60034; IEC 61800; NEMA ICS 2.
We select starting methods & run voltage-dip studies.