Home/Knowledge/Motor starting

Motor Starting Method

Motors draw 6–7× FLC at start — the method limits inrush so voltage holds and load gets torque.

Back to Knowledge Hub
Quick pick (TL;DR)
  • Small motors / strong supply → DOL (simplest, full torque).
  • Medium with light start → star-delta (cuts inrush to ~⅓ but only ⅓ torque).
  • Pumps/fans where you want a smooth ramp & less inrush → soft starter.
  • Need speed control, energy saving or high inertia → VFD.
  • Always check the supply can hold voltage dip within ~15% during start.

Step 1 — Choose the method

MethodStart currentStart torqueUse for
DOL6–7× FLCFullSmall motors
Star-delta~⅓ (2–3×)~⅓Light-start loads
Soft starter2.5–4×ControlledPumps, fans
VFD~1–1.5×ControlledSpeed control

Step 2 — Voltage-dip check

90 kW: DOL vs soft start
Given FLC = 166 A , source short-circuit = 6000 A Option A — DOL I_start = 6.5 × 166 = 1079 A approx dip ≈ I_start / I_sc = 1079 / 6000 18% > 15% limit → NG Option B — soft start I_start = 3.0 × 166 = 498 A approx dip ≈ 498 / 6000 8% ≤ 15% → OK Answer soft starter, start current 3×FLC

Volt-dip ≈ start current ÷ source fault level. DOL dips 18%; soft starter keeps within limits.

Step 3 — Other deciders

  • Star-delta only for light-start loads.
  • Frequent starts / speed → VFD.
  • Soft starter needs bypass contactor.

Starting voltage-dip calculator

Inrush & approximate bus voltage dip
I_start = factor × FLC; dip ≈ I_start / source fault. Keep ≤ ~15%.
First-order screening — a real study models impedances & torque curves.

Common mistakes

  • Star-delta on a loaded conveyor.
  • DOL on a weak supply.
  • VFD without harmonic mitigation.

Requisition & datasheet

  • Power, voltage, FLC, load, inertia.
  • Method, start current, volt-dip, protection.

Frequently asked questions

What should I know about Motor Starting Method?

Small motors / strong supply → DOL (simplest, full torque). Medium with light start → star-delta (cuts inrush to ~⅓ but only ⅓ torque). Pumps/fans where you want a smooth ramp & less inrush → soft starter. Need speed control, energy saving or high inertia → VFD. Always check the supply can hold voltage dip within ~15% during start.

Which standards or codes apply?

IEC 60947-4-1 (starters & contactors), IEC 60034 (motors), IEC 61800 (VFD drives), NEMA ICS 2.

Standards — IEC 60947-4-1; IEC 60034; IEC 61800; NEMA ICS 2.

Related guides

Need a motor-starting study?

We select starting methods & run voltage-dip studies.